Performance tables
for exchangers of MAX key line

Primary medium: Saturated steam – absolute pressure of saturated steam: 0,5 MPa,
Saturated steam – absolute pressure of saturated steam: 0,5 MPa
Secondary medium: boiler water 67,5°C / 92,5°C hot
Exchange type Performance Throughput Throughput Pressure loss
    Prim. Second. Second.
  kW kg/sec kg/sec kPa
MAX H0K 63,0 0,021 0,602 9,7
MAX H1K 149,0 0,065 1,43 30,0
MAX H2K 257,0 0,11 2,45 15,6
MAX 2.4-1.2-8 188,0 0,076 1,8 30,0
MAX 3.4-2-8 269,0 0,11 2,56 30,0
MAX S1X 573,0 0,23 5,46 30,0
MAX 5.4-4-8 501,0 0,21 4,78 30,0
MAX 6.4-5.4-8 594,0 0,25 5,68 30,0
MAX 9.4-10-8 1377,0 0,556 13,15 30,0
MAX 12.4-16-8 1683,0 0,68 16,10 30,0
MAX 17.4-40-10 3679,0 1,49 35,12 30,0

Primary heat-transfer fluid: Saturated steam – absolute pressure of saturated steam: 0,5 MPa,
temperature of saturated steam: c. 151°C
Secondary heat-transfer fluid: water – domestic hot water 10°C / 55°C
Exchange type Performance Throughput Throughput Pressure loss
    Prim. Second. Second.
  kW kg/sec kg/sec kPa
MAX H0K 215,0 0,084 1,13 30,0
MAX H1K 268,0 0,097 1,43 30,0
MAX H2K 596,0 0,25 3,16 25,4
MAX 2.4-1.2-8 338,0 0,13 1,8 30,0
MAX 3.4-2-8 483,0 0,18 2,56 30,0
MAX S1X 1031,0 0,39 5,46 30,0
MAX 5.4-4-8 904,0 0,34 4,78 30,0
MAX 6.4-5.4-8 1070,0 0,40 5,68 30,0
MAX 9.4-10-8 2478,0 0,93 13,15 30,0
MAX 12.4-16-8 3030,0 1,13 16,10 30,0
MAX 17.4-40-10 6623,0 2,46 35,12 30,0